90 amp front access dc power system

Product Information

Aspiro 2U M37 is a 2RU high 19” rack-mounted, integrated 90 Amp Front Access DC power system providing an output of -48VDC. The highly configurable system accommodates up to 4 Aspiro family high efficiency hot-swap rectifiers.

A total current of 90A is available which may be shared between the load and battery charge current, the latter being programmable via the controller. The rectifiers are internally fan cooled with speed control which is a function of load and temperature, keeping acoustic noise to a minimum.

The system includes a Low Voltage Battery Disconnect (LVBD) as standard while a Partial Load Disconnect (PLD) is available in some configurations. As standard, four form-C relay outputs provide the alarms for remote use. Two digital inputs and outputs are also available along with connections for battery symmetry measurement and a number of analog inputs.

The Aspiro 2U M37 90 Amp Front Access DC power system is available in four basic configurations; 2 x Battery Breakers with LVBD and 2 x Load Breakers, 2 x Battery Breakers with LVBD and 2 x Load Breakers plus 6 x GMT load fuses (30A max. total), 1 x Battery Breaker with LVBD and 1 x Load Breaker plus 10 x GMT load fuses (100A max. total), 1 x Battery Breaker with LVBD and 1 x Load Breaker plus 16 x GMT load fuses. The first two can be factory configured with 1 x battery breaker with LVBD, 1-3 x load breakers, or 1–3 x load breakers with PLD.

THREE YEAR WARRANTY

Features and Options
  • 95% Efficiency Rectifiers
  • 90A / 4.8kW Capacity
  • 1 or 2 Bulk DC Outputs
  • Intelligent Battery Management
  • Up to 16 Auxiliary Load Circuits
  • Remote Monitoring & Control
  • Field Replaceable Controller
  • Ethernet Comm. with SNMPv3
  • 3 LED Alarm/Status Indicators
  • 4 Form-C Relay Alarms
  • LVBD and Optional PLD
  • LCD Display/Touchpad
  • Easy Installation
  • NEBS Level 3 Compliant
SPECIFICATIONS
 
OUTPUT
System Voltage-48VDC nominal | -53.5 float (factory default setting, user adjustable)
Maximum Capacity @ 120VAC nominalLoad - 60A
Battery - 60A discharge | 30A charge (s/w controlled)
Maximum Capacity @ 230/400VAC nominalLoad - 60A
Battery - 60A discharge | 30A charge (s/w controlled)
No. Rectifier Slots4
 
DC DISTRIBUTION
Bulk Load Circuits 1, 2 or 3 x up to 100A MCB
Auxiliary Load Circuits6, 10 or 16 x up to 15A GMT Fuses
Battery Circuits 1 or 2 x up to 100A MCB
 
INPUT
Voltage (nominal)

1-phase 100-120/200-240VAC (L + N + PE)
Dual Phase (L1 + L2 + PE)

Frequency47-63Hz
Maximum Input Current10.5A @ 100-120VAC | 7A @ 200-240VAC
Rectifier Power Factor>0.98 (typical)
 
MONITORING & CONTROL (ACX Advanced Controller)
Alarm Relays4
Local Interface 4 x 20 LCD, 4-key menu, USB / RS232, microSD card slot (4GB max,) for data logging
Remote Interface Ethernet / Modem using PowCom™ software package
Ethernet port allows monitoring and control over a TCP/IP network.
Web browser support + SNMPv3.
LED IndicationsGreen - System ON; Yellow - Message(s); Red LED - Alarm(s)
External Digital I/O 2 x Inputs, 2 x Outputs (Open Collector)
 
BATTERY MANAGEMENT
Symmetry Inputs6 or 12 (can be redefined as analog inputs up to 100VDC)
Low Voltage Battery Disconnect (LVBD)1 x 125A Programmable
Partial Load Disconnect (PLD)1 x 125A Programmable (Optional)
Temperature Compensated ChargingProgrammable
 
COMPLIANCE
EMCEN 300 386 ; EN61000-6-3 (Emission) ; EN61000-6-2 (Immunity)
SafetyIEC60950-1:2005 2 Ed. +A1:2009
 
ENVIRONMENTAL
Operating Temperature-40ºC to +65ºC (derated above +55°C)
Storage Temperature-40°C to +85°C
Shock & Vibration NEBS Level 3
 
MECHANICAL
Dimensions, ins (mm) 19.0 (483) W x 3.4 (87) H x 21.8 (554) D
Mounting 19" Mid-Mount | 23" with optional adaptors
Weight 22lbs (10kg)
INTELLIGENT BATTERY MANAGEMENT
(PROVIDED VIA ACX ADVANCED CONTROLLER)
Battery Disconnection Provides voltage controlled disconnection of batteries.
Boost Charging Manual time controlled or automatic boost charging with adjustable time and voltage levels.
Battery Tests Automatic or manual testing of batteries up to six times per year with a 10 test memory. Variables include test duration and end voltage.
Battery discontinuance test to ensure battery connection.
Enhanced Battery Monitoring Monthly logging of essential battery parameters including temperature, temperature hours, current, charging voltage and symmetry voltage, Data logged for 5 years.
Site Logs System tools developed to assist site management. Daily peak load and statistic logs available.
Symmetry Measurement Optional tool that measures batteries for early detection of thermal runaway.
Temperature Compensation Charging

Allows continuous adjustment of output voltage according to battery temperature.
Features include adjustable compensation factor and separate thresholds for high temperature alarms.

Load Shedding (PLD) Optional feature that allows voltage or time controlled disconnection of non-essential load.  

STANDARD SYSTEM CONFIGURATIONS
Base Model Front View Battery Circuits Load Circuits
MN010-Axx11 2 MCBs 2 MCBs
MN010-Axx31 2 MCBs 6 GMT Fuses
MN010-Axx41 1 MCB 1 MCB
10 GMT Fuses
MN010-Axx61 1 MCB 1 MCB
16 GMT Fuses

AC INPUT OPTIONS
Base Model Rear View AC Input  
MN010-ASxyy 1 Terminal Block  
MN010-ADxyy 2 Terminal Blocks  
MN010-ANxyy 4 IEC60-320 Inlet