Scimitar

3000 watt inverters

Product Information

The SIMITAR 3000 Series are 3000 watt inverters which are 19” rack-mountable and only 2RU high. Different models operate from a 12, 24 or 48 VDC source and produce a sine-wave 115 or 230 VAC output.

The tightly regulated low distortion 50 or 60Hz sine wave is produced by DSP controlled power circuits using an advanced high frequency, pulse-width modulation technique which achieves up to 92% efficiency.

A built-in Static Transfer Switch allows connection of a utility or other AC power source which can be switched to the load automatically in the event that the inverter switches off.
In normal operation these inverters isolate the load from wide voltage swings , transients and noise usually present in the AC utility and which can cause equipment reliability problems.

Output voltage and frequency are programmable from the front panel, as well as Baud Rate for the RS232 communications interface which can be used for remote monitoring.

TWO YEAR WARRANTY

Features and Options
  • 19-Inch x 2RU Rack Mounting
  • 3000W Output Capacity
  • 115VAC or 230VAC Output
  • 50 or 60Hz Low Distortion Sine Wave
  • 12, 24 or 48 VDC Input
  • -20 to +50°C Operating Temperature
  • Static Transfer Switch Built-in
  • Adjustable Output Voltage
  • Programmable Frequency (DIP switch)
  • Powers Reactive Loads
  • LED Status Display
  • Relay Alarm Output
SPECIFICATIONS
 
INPUT
Voltage

12VDC (10-16VDC)
24VDC (20-32VDC)
48VDC (42-62VDC)

Current (max.) 349A @ 12V
171A @ 24V
81A @ 48V
 
OUTPUT
Voltage

100-120VAC (adjustable)
200-240VAC (adjustable)

Power 3000W continuous | 6000W peak
Surge Rating 3200W for 3 minutes, 3500W for 3 seconds
Frequency 50Hz or 60Hz ±0.05% (switch selectable)
Efficiency 86-92% depending on model
Output Waveform Pure Sine Wave <3% THD (R Load)
 
TRANSFER FUNCTION (-STS OPTION)
AC Input Range 90-130VAC (110VAC nominal)
180-260VAC (230VAC nominal)
Frequency 47-63Hz
Transfer Time 4-6mS
Alarm Relay Form-C dry contacts, indicates presence of AC Utility supply
 
OTHER TECHNICAL DATA
Protection Output Overload; Output Short Circuit; Input Reverse Polarity (fuse); Input Undervoltage; Input Overvoltage; Over Temperature
Alarms General alarm signal activated by an open photo-relay if in fault mode, available at rear signal connector
Display OVP - UVP - OTP - OLP - VAC - AMP - WATT - VDC - TEMP - Hz
Control Port RS232C - Baud Rates - 2400, 4800, 9600, 19200 (switch selectable)
SNMP (Option) Operates in conjunction with NetAgent UPS SNMP Agent
Temperature Range Operating: -20°C to +50°C
Storage: -30°C to +70°C
MTBF > 98,000 hrs @ 25°C ambient, nominal output voltage & full load
 
DESIGN STANDARDS
Safety EN60950-1
EMC

120VAC Models:
FCC CFR Title 47 Part 15 Subpart B: 2008 Class A
CISPR 22: 2005
ANSI C63.4: 2003

230VAC Models:
EN55022:2006+A1: 2007, Class A
EN55024: 1998+A1: 2001+A2: 2003
EN61000-3-2: 2006
EN61000-3-3: 1995+A1: 2001+A2: 2005
IEC61000-4-2 Ed. 1.2: 2001-04
IEC61000-4-3 Ed. 3.0: 2006
IEC61000-4-4: 2004
IEC61000-4-5 Ed. 2.0: 2005
IEC61000-4-6 Ed. 2.2: 2006
IEC61000-4-8 Ed. 1.1: 2001-03
IEC61000-4-11 2nd Ed.: 2004-03

 
MECHANICAL
Case Dimensions, inches (mm) 16.7 (424) W x 3.5 (88) H x 17.5 (445) D
Weight31.5lbs / 14.3Kg
Mounting 19" Rack, 2RU
STANDARD MODELS
Model
Number
Output
Power
Output
Voltage 1, 2
Input
Voltage
SNMP 3
INV1230R-B 3kW - Continuous
6kW - Peak
115VAC 12VDC Option
INV2430R-B 24VDC Option
INV4830R-B 48VDC Option
INV1230RH-B 230VAC 12VDC Option
INV2430RH-B 24VDC Option
INV4830RH-B 48VDC Option
Notes:
  1. 115VAC models are shipped pre-programmed to 60Hz.
    230VAC models are shipped pre-programmed to 50Hz.
  2. 115VAC models can be adjusted between 100 and 120VAC.
    230VAC models can be adjusted between 200 and 240VAC.
  3. To specify the SNMP option add ‘S’ to the end of the model number, e.g. INV4830R-BS.