Product Information

The SAGEON II Power Module 600Amp Bulk DC Power System is available in two bulk power sizes 600A (N+1) and 400A (N+1), the Sageon II Power Module 600Amp Bulk DC Power System provides the flexibility to put power where it is needed.

The Sageon II Power Module 600Amp Bulk DC Power System consists of a power frame that includes the Sageon Controller and Rectifiers, mechanical mounting for up to nine rectifiers in the 400A offering and up to thirteen rectifiers in the 600A system. Each unit comes with an AC conduit box for ease of installation.

In addition to the basic control functions, the Sageon II Power Module 600Amp Bulk DC Power System supports all the advanced functionality available in all Sageon Family of products including: remote monitor and control, battery testing, individual cell monitoring, programmable battery recharge current, and site monitoring.

THREE YEAR WARRANTY

Features and Options
  • High Power Density
  • 400A or 600A Capacity
  • 24VDC or 48VDC
  • 2400W Hot-Swap Rectifiers
  • Battery Testing
  • Battery Monitoring
  • Remote Monitoring & Control
  • Programmable Battery Recharge
  • Field Replaceable Controller
  • LCD Display/Touchpad
SPECIFICATIONS
 
INPUT
Voltage RangeAC 85-300VAC (L-N. 1ph, or 3ph-Y, 3ph-delta [option].
Fully protected up to 440VAC (L-N)
Frequency47-63Hz
Inrush Current<16A RMS per rectifier
THDLine Harmonics meet EN61000-3-2
Power Factor>0.98 for >50% output power
 
OUTPUT
Voltage Range-48VDC systems: adjustable range 42.0V to 59.5V
+24VDC systems: adjustable range 21.0V to 30.0V
Current Limit-48VDC systems: 60A max. per rectifier, fully adjustable
+24VDC systems: 50A max. per rectifier, fully adjustable
Power Limit

-48VDC systems: 2400W per rectifier
+24VDC systems: 1400W per rectifier

Efficiency>90% at 100% output power for 48VDC systems
>88% at 100% output power for 24V systems
Regulation±1% or better over line, load and temperature
Noise.1% pk-pk max.
Line Regulation<1mV RMS Psophometrically weighted
<32dBrnC Voiceband
<10mV RMS and <100mV peak-to-peak (10kHz-100MHz)
 
PROTECTION
Short CircuitCan sustain short circuit at output terminals indefinitely
Reverse Battery PolarityInternal fuse at output of RECTIFIER, integral battery circuit breakers and detection/disconnection circuitry
High Voltage ShutdownRectifier shuts down if output exceeds programmed overvoltage limit
Electrostatic Discharge (ESD)IEC 61000-4-2 (Level 4: Air 15kV, Contact 8kV)
AC SurgeIEC 61000-4-4 (EFT), Level 4
IEC 61000-4-5 (Impulse), Level X: 6kV/3kA
IEC 61000-4-12 (Ringwave), Level X: 6kV/500A
RF ImmunityIEC 61000-4-3 (Radiated), Level 4
IEC 61000-4-6 (Conducted), Level 3
RF EmissionsCISPR 22 Class B, (Conducted & Radiated)
 
ENVIRONMENTAL
Operating Temp. Range-40°C to +55°C (Full Load)
Derating Operation50% power at +70°C
Storage Temp. Range-40°C to +70°C
Humidity0 to 100% relative humidity, condensing
Acoustic Noise<60dB (A weighting)
 
PHYSICAL SPECIFICATIONS
Dimensions, inches (mm)8.57-15.75 (222-400) H x 19.0 (483) W x 14.0 (355) D - see configurations table
Weight81-127lb (37-58kg) - see configurations table
 
COMPLIANCE
EMCETSI EN 300 386 V1.3.2 (2002-12)
SafetyIEC 60950, UL/CSA 60950
EnvironmentalETSI EN 300 019
STANDARD SYSTEM CONFIGURATIONS
TypeOutput
Current
ExampleHeightWeight
List 40400A5RU81lb | 37kg
List 41400A7RU101lb | 46kg
List 60600A7RU107lb | 49kg
List 61600A9RU127lb | 58kg